Summer Ventilation Test of 200-occupant Basement Shelter in Milwaukee, Wisconsin


Book Description

Forced and natural ventilation tests performed on a partially below grade fallout shelter in Milwaukee, Wisconsin, during the month of August 1963 revealed that 6.1 cubic feet per minute per occupant of ambient ventilating air would be necessary on a typical warm summer day (Milwaukee 5% Summer Design) to maintain this shelter at a survivable 85 deg.F. effective temperature. The shelter as tested (during cool summer weather) required 4.7 cfm per occupant; this result was analytically corrected to obtain the warm summer day ventilation requirement. Similar forced ventilation tests were performed using typical hot, moderately humid air as would be expected in the south central part of the country. When corrected to these design conditions, a ventilation rate of 13.1 cfm per occupant would be needed to maintain 85 deg. F. effective temperature in the shelter.




Summer Ventilation Test of a Corridor-type Fallout Shelter in Milwaukee, Wisconsin


Book Description

Ventilation tests of a 240-man above-grade fallout shelter were performed using simulated occupants. Conditioned air and/or outside air were supplied to the corridor-type shelter at rates varying from 3 to 15 cfm. A natural ventilation test was made with one window opened at each end of the 190-foot long shelter. With winds ranging from 4 to 15 mph, the ventilation rate varied from 8 to 11 cfm per person simulated. Much larger ventilation rates could be obtained if more windows had been opened. This test series is one of many performed to determine the minimum equipment requirements necessary to maintain a habitable shelter atmosphere.




Evaluation of 200-Person Shelter (ventilation)


Book Description

Observations were made of the thermal environment in the basement portion of a box shaped reinforced concrete 200 person shelter when the shelter was supplied with a minimum quantity of ventilation air. Also, an evaluation was made of the distribution of the ventilation air in the shelter as measured by variations in effective temperature, when the air was supplied through a duct system and through a single point source. Ventilation air conditioned to simulate a 1% design day in the Washington, D.C. area (i.e. air at dry bulb and wet bulb temperatures which will not be exceeded more than 1% of the time), was supplied to the shelter area tested. Approximately 100 simulated occupants were placed in the shelter basement to generate the same amount of heat and moisture as 100 human occupants. When conditioned air was supplied at a minimum rate of 3 cfm per person, effective temperatures as high as 90 deg were attained and maintained within the shelter. Based on current standards for the thermal environment in shelters, it is concluded that a minimum ventilation rate of 3 cfm is not adequate for cooling this shelter space.




Summer Ventilation Tests - P. S. No. 21 Fallout Shelter - Bronx County, N.Y.


Book Description

The partially below-grade basement cafeteria shelter was tested with both natural ventilation and forced ventilation at controlled temperatures. The shelter floor area was 2,550 square feet and occupancy was simulated by aggregate, electro-mechanical Simocs. In addition, an interior corridor shelter area on the second floor was tested with natural crosswind and updraft ventilation. The recorded data were then applied to the solution of shelter heat balance equations, and also used to estimate the effect of different outside air conditions and occupancy rates on the shelter effective temperature.




Ventilation Tests of an Identified Basement Shelter in Houston, Texas


Book Description

Tests were conducted in Houston, Texas during October, 1962 in a partly below-grade shelter area to determine the minimum ventilation rates required to sustain life during long periods of occupancy in community size fallout shelters. High earth temperatures and weather equivalent to that in summer provided external conditions resulting in the maximum ventilation requirements for this location. Aggregate simulated occupants duplicated the effect of the metabolic heat loads of 140 to 400 humans. Test results indicated that, with average August weather prevailing, at least 13 cfm per occupant of ventilation capacity was required to sustain life if no system for cooling the shelter air was provided.




Simulated Occupancy Test - Basement of Central Stores Building, Gainesville, Florida


Book Description

The purpose of this test was to determine the effect of occupants on environmental conditions within a survival shelter. Environmental conditions for the purpose of this test were gaged by changes in temperature and humidity at certain selected points within the shelter area. Changes in air flow and in the number of simulated occupants were made at various times during the test in an attempt to establish an optimum relationship between occupants, floor area and air flow. It was concluded that a ventilation air rate of 3 cfm per occupant was inadequate during summer occupancy in this region. In order to maintain the effective temperature in the shelter, at, or below a value of 85 F, approximately 14 cfm/occupant of outside air must be provided. More detailed results and conclusions are presented in the body of this report.




New York State Codes


Book Description







2018 International Plumbing Code Turbo Tabs, Loose-Leaf Version


Book Description

An organized, structured approach to the 2018 INTERNATIONAL PLUMBING CODE Loose leaf Version, these TURBO TABS will help you target the specific information you need, when you need it. Packaged as pre-printed, full-page inserts that categorize the IPC into its most frequently referenced sections, the tabs are both handy and easy to use. They were created by leading industry experts who set out to develop a tool that would prove valuable to users in or entering the field.




The Antiquities of Wisconsin


Book Description