Book Description
The results indicate that a ventilation rate of 3 cfm/occupant is more than adequate to maintain long-term, thermally habitable, shelter environment for 330 occupants for the encountered winter and/or spring conditions. With zero ventilation, the shelter can accommodate from 48 to 90 people. The air leakage varied from 0.043 to 0.055 cfm/square foot of exposed shelter surface. For winter and/or spring conditions, the heat transfer through the shelter surfaces is important in lowering the shelter effective temperature.